The system watches the pressure in the sprinkler pipework against preset values all the time – and responds on its own, with no operator.

Operation

The jockey pump, with the pressure vessel and a set of pressure switches, holds the set pressure. It makes up for small leaks and temperature changes and watches the mechanical integrity of the pipework.

When one of the sprinkler heads opens, a falling-pressure signal is given. The control panel starts the first main electric pump and gives an audible and visual alarm. Until the pump runs up to speed, water reaches the sprinkler system from the pressure vessel.

If the power fails or the electric pump fails, the low pressure in the system starts the second electric or diesel pump.

If walls collapse or parts of the pipework are torn and the flow rises, the low-pressure signal starts as many pumps at once as are needed.

After the event the pumps are switched off by hand and set to “Standby”. The jockey pump automatically refills the pipework with water and keeps the system ready.

Main advantages

  • European certificates
  • Easy design, based mainly on the required pressure and flow
  • Small overall dimensions that cut building costs
  • Its own base frame
  • Optimal cost
  • No dependence on feedback, signals or an operator
  • Fully automatic
  • Self-testing
  • Service support

Description

The pump systems we offer are fully autonomous, with automatic microprocessor control. They reach pressures from 3.5 to 18 bar and flows from 6 m³/h to 800 m³/h, with electric and diesel pumps – to supply fire, sprinkler and deluge systems, hydrants, pressure booster and cooling systems, water towers and more.

The pump set is assembled from standardised, certified components. One layout includes:

  1. One, two or more main electric and engine-driven pumps
  2. Relief valves
  3. Check valves
  4. Microprocessor control
  5. Shut-off valves
  6. Electrical control panels
  7. Pressure switches and test gauges for each pump separately
  8. A common discharge manifold with flanges to connect to the pipework
  9. A pressure vessel of suitable volume that supplies water the moment a sprinkler head opens and keeps the flow until the pumps run up
  10. Flexible connections for the diesel pumps
  11. A monitoring battery charger
  12. An oil sump heater for the diesel engine
  13. A metal base frame for the system
  14. Duplicated batteries
  15. A jockey pump that keeps the whole pipework ready and pressurised, up to the furthest point of the sprinkler system